One Stop

Level 2 specification

NR/L2/TEL/30085

Specification for the Maintenance of Electronic PABX Concentrators (formerly NR/WI/TEL/30085)

Issue 2, 7 March 2009

Maintenance regime for electronic PABX switches used as operational telephone concentrators in signal boxes and electrical control rooms: user console and handset tests (typically 6 monthly), equipment inspection, voltages, alarms, clock and system data backup (typically 12 monthly), with one appendix per make: V-Band, Meridian, Syntegra, Realitis/iSDX, MD110, Hicom/HiPath, BP50, Mitel Imagination and Tenovis.

Clause map — what each clause deals with

1PurposeMaintaining operational PABX concentrators to reduce deterioration failures
2ScopeSwitches acting as operational concentrators; business PABXs, power plant, Keltek TSSUs and voice recorders are covered by other standards; remote nodes treated as separate switches
3DefinitionsAbbreviations used including CDR, DC/AC, ESSD, ESP, HMI, EMC, ICC, PABX, TSSU
4ResponsibilitiesAgree effects with signaller, ESD precautions, off-site backup reachable within restoration SLA, follow manufacturer documents and record their issue, don't rely on built-in meters
Appendix AMaintenance of V-Band6 monthly console, label, handset and call function tests; 12 monthly equipment inspection, voltages, cleaning, clock, alarms and data backup
Appendix BMaintenance of Meridian6 monthly user console tests and 12 monthly equipment checks at main and remote sites
Appendix CMaintenance of Syntegra6 monthly console tests including standby console; 12 monthly equipment inspection and data backup
Appendix DMaintenance of Realitis / iSDXWeekly file server, link and automatic backup checks with tape rotation; 6 monthly console tests; 12 monthly equipment at main and satellite sites
Appendix EMaintenance of MD1106 monthly console, 12 monthly equipment and backup, plus weekly remote system check of clock, blocked equipment and fault/alarm log
Appendix FMaintenance of Hicom (Hipath)Console tests with Stratus server and shoe-box PC cleaning and touchscreen recalibration; yearly equipment checks and Stratus database backup
Appendix GMaintenance of BP506 monthly console tests and 12 monthly equipment inspection with system data backup
Appendix HMaintenance of Mitel Imagination6 monthly console tests including press-to-talk handsets and 12 monthly equipment inspection and backup
Appendix IMaintenance of TenovisSingle 3 monthly service covering equipment inspection, cleaning, checks and system data backup